Siemens 5SJ4213-8HG41 — 2-Pole MCB (DIN Rail)

Siemens 5SJ4213-8HG41 SENTRON MCB, 2P D-curve, 10 kA

MPN5SJ4213-8HG41
Active

Siemens SENTRON 5SJ4213-8HG41 miniature circuit breaker, 2-pole, D tripping characteristic, 10 kA (EN 60898), 15 kA (IEC 60947-2), 400 V AC, snap-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4213-8HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SJ4213-8HG41 — Electrical
ParameterValue
Number of poles2
5SJ4213-8HG41 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage category3
5SJ4213-8HG41 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors, IP 40 in the handle range
5SJ4213-8HG41 — Environmental
ParameterValue
Pollution degree3
5SJ4213-8HG41 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA

Product details

The Siemens 5SJ4213-8HG41 is a 2-pole SENTRON miniature circuit breaker with a D tripping characteristic, rated 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. The D-curve means it tolerates high inrush currents — typical for motor, transformer, or welding loads — without nuisance tripping on startup. It snaps onto standard DIN rail and occupies 2 modular width units (36 mm wide), making it a direct fit for most distribution panels.

Frequently asked questions

What is the breaking capacity of 5SJ4213-8HG41?

10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC.

What is the D tripping characteristic used for?

The D-curve allows higher inrush current without tripping — suited for motor, transformer, and welding loads where startup current can briefly exceed the steady-state rating.

Where can I buy 5SJ4213-8HG41?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

Will 5SJ4213-8HG41 fit a panel designed for 5SY4304-7CV?

Both are 2-pole MCBs on standard DIN rail, but the 5SY series uses a different tripping characteristic and breaking capacity. The 5SJ4213-8HG41 is a D-curve 10 kA part; the 5SY4304-7CV is a C-curve variant. They are not direct drop-in replacements without verifying the required curve and interrupting rating for the circuit.

MPN
5SJ4213-8HG41