Rated breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC, with a DC rating of 60 V. That dual rating covers both residential-style (EN) and industrial (IEC) installations, giving the panel designer flexibility in which standard governs the coordination study. Snaps onto standard DIN mounting rail, accepts any mounting position, and carries an IP20 rating with connected conductors (IP40 in the handle area).
Integration notes
Rated insulation voltage 440 V AC. Neutral conductor is not switched — this is a 2-pole breaker for line and load, not a switched-neutral device.