Skip to main content
Siemens 5SJ4218-8HG42 — 2-Pole MCB (DIN Rail)

Siemens 5SJ4218-8HG42 SENTRON MCB, 2P D 15A

MPN5SJ4218-8HG42
Active

Siemens SENTRON 5SJ4 series, 2-pole miniature circuit breaker, D tripping characteristic, 15 A rated at AC, 60 V DC max, 36 mm wide, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4218-8HG42 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SJ4218-8HG42 — Electrical
ParameterValue
Number of poles2
5SJ4218-8HG42 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage category3
5SJ4218-8HG42 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height121 mm
Depth70 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors, IP 40 in the handle range
5SJ4218-8HG42 — Environmental
ParameterValue
Pollution degree3

Product details

The 15 A rating holds at 30 °C and 40 °C ambient; above that it derates to 14.6 A at 45 °C, 14.1 A at 50 °C, 13.6 A at 55 °C, and 13.2 A at 60 °C, so factor your panel ambient into the load calculation.

Panel fit and environment

Width is 36 mm (2 modular units), depth 70 mm, height 121 mm. Snaps onto standard mounting rail (DIN rail) in any position. Sealable, so a panel lockout tag can be applied after commissioning.

Frequently asked questions

How do I get current pricing and availability for 5SJ4218-8HG42?

Submit an RFQ. Pricing and stock are confirmed at quote time through independent distribution channels.

What is the D tripping characteristic used for?

The D-curve (10–20× In magnetic trip) is designed for loads with high inrush current: motors, transformers, welding equipment, and discharge lighting. It prevents nuisance tripping on startup surges while still providing short-circuit protection.

What is the thermal derating for 5SJ4218-8HG42?

The 15 A rating holds at 30 °C and 40 °C. It derates to 14.6 A at 45 °C, 14.1 A at 50 °C, 13.6 A at 55 °C, and 13.2 A at 60 °C. Factor your panel ambient temperature into the load calculation.

What compliance documentation does this brand provide for 5SJ4218-8HG42?

The product is designated per EN 61346-2 and IEC 81346-2 (function code F). It is halogen-free and silicon-free, rated for pollution degree 3 and overvoltage category 3. Standard manufacturer declarations for RoHS and REACH are available on request.

MPN