Siemens SENTRON 5SJ4, miniature circuit breaker, 2-pole, D-characteristic 25 A, 10 kA per EN 60898, DIN-rail mount, IP20/IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4225-8HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SJ4225-8HG41 — Electrical
ParameterValue
Number of poles2
5SJ4225-8HG41 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage category3
5SJ4225-8HG41 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors, IP 40 in the handle range
5SJ4225-8HG41 — Environmental
ParameterValue
Pollution degree3

Product details

The Siemens 5SJ4225-8HG41 is a SENTRON 5SJ4 miniature circuit breaker with a D tripping characteristic, rated 25 A at 30 °C and 40 °C, and 10 kA breaking capacity per EN 60898. The D-curve means it tolerates the high inrush currents typical of motor loads, transformers, and welding equipment — where the short-circuit trip threshold is 10 to 20 times rated current — without nuisance tripping on startup.

Thermal derating and ambient limits

Rated 25 A at 30 °C and 40 °C, the breaker derates to 24.3 A at 45 °C, 23.8 A at 50 °C, 23.1 A at 55 °C, and 22.5 A at 60 °C. If the panel ambient runs above 40 °C, size the branch circuit for the derated value, not the nameplate 25 A. The unit operates from -40 °C to 75 °C ambient, covering unheated enclosures and high-heat machine cabinets.

Sourcing posture

This 2-pole D-curve 25 A MCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. For a BOM line or a line-down replacement, submit an RFQ with your target quantity and delivery window.

Frequently asked questions

What is the breaking capacity of 5SJ4225-8HG41?

It is rated 10 kA per EN 60898, which certifies the breaker can safely interrupt fault currents up to 10,000 A under standard test conditions.

Where can I buy 5SJ4225-8HG41 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ with your quantity and target delivery date; availability and current pricing are confirmed at quote time.

What is the difference between 5SJ4225-8HG41 and 5SJ6220-6?

The 5SJ6220-6 is a 2-pole C-curve 20 A MCB versus the D-curve 25 A 5SJ4225-8HG41. Both mount on standard DIN rail in 2 MWU, so they share the same footprint, but the D-curve on this part handles higher inrush (10–20× rated) for motor and transformer loads, while the C-curve (5–10×) suits general distribution. They are not direct drop-in replacements without verifying the trip coordination and load current.