Skip to main content
Siemens 5SJ4232-8HG41 — 2-Pole MCB (DIN Rail)

Siemens 5SJ4232-8HG41 SENTRON MCB, 2-Pole D-Curve, 10kA

MPN5SJ4232-8HG41
Active

Siemens SENTRON 5SJ4 series, miniature circuit breaker, 2-pole, D tripping characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC / 60 V DC, 2 MW units, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4232-8HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SJ4232-8HG41 — Electrical
ParameterValue
Number of poles2
5SJ4232-8HG41 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage category3
5SJ4232-8HG41 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors, IP 40 in the handle range
5SJ4232-8HG41 — Environmental
ParameterValue
Pollution degree3
5SJ4232-8HG41 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA

Product details

The Siemens 5SJ4232-8HG41 is a 2-pole miniature circuit breaker from the SENTRON 5SJ4 series, designed for branch-circuit overcurrent protection in industrial control panels. The interrupting capacity is rated at 10 kA per EN 60898 and 15 kA per IEC 60947-2, so it clears faults up to that level without cascading upstream; the higher IEC figure applies when the breaker is applied per the industrial standard rather than the residential one. Rated AC voltage is 400 V, DC voltage 60 V, with an insulation voltage (Ui) of 440 V AC. Pollution degree 3 and overvoltage category 3 mean it's rated for the conductive environment inside a typical industrial enclosure — not a clean-room panel, but a standard IP54 cabinet with some dust and condensation. The breaker mounts on standard DIN rail (35 mm) in any position, and occupies 2 modular width units (36 mm total width).

Deployment context and environmental limits

This MCB is suited for mechanical engineering and industry applications per the manufacturer's designation. The ambient temperature range spans -40 °C to 75 °C, with a maximum 95% humidity — wide enough for unheated plant floors or outdoor cabinets in temperate climates, though the upper limit of 75 °C means it can sit near heat sources inside a panel without derating concerns. Vibration resistance is specified at 50 m/s² over 25 to 150 Hz and 60 m/s² at 35 Hz (4-second dwell), which covers the typical vibration profile of a motor control center or a panel mounted on a machine frame. The protection class is IP20 with connected conductors, and IP40 in the handle range — standard for a DIN-rail component inside an enclosure. EMC environment B means immunity to interference is not applicable — this is a passive protective device, not a sensitive electronic load.

Frequently asked questions

What are the key ratings for the 5SJ4232-8HG41?

It is a 2-pole D-curve MCB rated 400 V AC / 60 V DC, with interrupting capacity of 10 kA per EN 60898 and 15 kA per IEC 60947-2. The D curve trips magnetically at 10–20× rated current, suited for high-inrush loads.

Where can I buy the 5SJ4232-8HG41?

It is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — no stock count or lead time is published here, but the channel is active.

What compliance documentation does Siemens provide for this MCB?

The 5SJ4232-8HG41 carries ratings per EN 60898 and IEC 60947-2, and is designated as halogen-free and silicon-free. Specific RoHS, REACH, and UL documentation should be requested at quote time — the evidence does not list a UL mark or a specific declaration number.

Will the 5SJ4232-8HG41 drop into a panel specified around the 5SY4304-7CV?

Both are 2-pole DIN-rail MCBs from Siemens, but the 5SY4304-7CV uses a different tripping characteristic and interrupting rating. The 5SJ4232-8HG41 is a D-curve device; verify the existing panel's coordination study before swapping — the physical footprint (2 MW, 36 mm wide) is the same, but the trip behavior differs.

MPN
5SJ4232-8HG41