Siemens 5SJ4235-7HG41 — 35 A C-Curve MCB, Active Production
Thermal Derating & Ambient Range
At 30 °C and 40 °C ambient the breaker holds its full 35 A rating. At 45 °C it derates to 34 A, at 50 °C to 33.3 A, at 55 °C to 32.4 A, and at 60 °C to 31.5 A.