Skip to main content
Siemens 5SJ4303-8HG41 — 3-Pole MCB (DIN Rail)

Siemens 5SJ4303-8HG41 SENTRON MCB, 3P D-curve, 10kA/15kA

MPN5SJ4303-8HG41
Active

Siemens SENTRON 5SJ4 series, miniature circuit breaker, 3-pole, D tripping characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC / 60 V DC, 3 MW units, IP20/IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ4303-8HG41 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SJ4303-8HG41 — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-215 kA
Overvoltage category3
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
5SJ4303-8HG41 — Electrical
ParameterValue
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.8 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
5SJ4303-8HG41 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodon standard mounting rail
SealableYes
Accepts supplementary devicesYes
5SJ4303-8HG41 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Vibration resistance (IEC 60068-2-6)±1 mm at 5 to 25 Hz; 50 m/s² at 25 to 150 Hz

Product details

SENTRON 5SJ4 — D-curve MCB for motor and transformer circuits

Rated 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC, with a 60 V DC maximum rating — the higher IEC figure applies when the MCB is used in industrial panel applications where the standard permits the full 15 kA SCCR. Three-pole design occupies 3 modular-width units (54 mm) on standard DIN rail, installable in any orientation, with a 70 mm depth.

Snaps onto standard mounting rail; the 54 mm width (3 MW) and 70 mm installation depth leave room for side-by-side busbar feeders. Sealable design allows lockout/tagout (LOTO) application without removing the breaker; halogen-free and silicon-free construction meets clean-environment requirements for semiconductor or food-grade panels.

Listed as current production. The 5SJ4 series remains an active catalog line from Siemens SENTRON.

Rated frequency 50 Hz; vibration resistance 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz (4 sec) — tested for continuous operation on machinery with moderate vibration levels.

Frequently asked questions

Will 5SJ4303-8HG41 drop into a panel specified around 5SY4140-7 without rewiring?

Both are 3-pole MCBs on standard DIN rail, but the 5SJ4303-8HG41 uses a D tripping curve while the 5SY4140-7 uses a different characteristic. Verify the load's inrush profile before substituting — the physical footprint and terminal arrangement are compatible, but the protection coordination may differ.

MPN