Skip to main content
Siemens 5SJ4306-8HG41 — 3-Pole MCB (DIN Rail)

Siemens 5SJ4306-8HG41 SENTRON MCB, D-curve, 3-pole, 10kA

MPN5SJ4306-8HG41
Active

Siemens SENTRON 5SJ4 series, miniature circuit breaker, 3-pole, D characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC, 50 Hz, 3 MW units, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4306-8HG41 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SJ4306-8HG41 — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-215 kA
Overvoltage category3
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
5SJ4306-8HG41 — Electrical
ParameterValue
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)2.7 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
5SJ4306-8HG41 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodon standard mounting rail
SealableYes
Accepts supplementary devicesYes
5SJ4306-8HG41 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Vibration resistance (IEC 60068-2-6)±1 mm at 5 to 25 Hz; 50 m/s² at 25 to 150 Hz

Product details

Breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. Rated insulation voltage (Ui) is 440 V AC, so it's comfortable on 400 V line-to-line systems with margin. For DC circuits, it's rated 60 V maximum, which covers 48 V control buses and small battery banks. IP20 with connected conductors (IP40 in the handle area) is standard for enclosed panel mount; no washdown rating, so keep it behind the gland plate.

Integration — DIN rail, terminals, environment

That covers unheated warehouses, outdoor cabinets in temperate climates, and the heat rise inside a packed panel. Vibration resistance is 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz (4 s) — enough for machine-mounted subpanels on conveyors or presses.

Frequently asked questions

Where can I buy 5SJ4306-8HG41 and how do I get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is 5SJ4306-8HG41's breaking capacity at 400 V?

10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. The IEC figure is the one to use for industrial panel coordination.

Will 5SJ4306-8HG41 drop into a panel specified around 5SY4304-7CV without rewiring?

Both are 3-pole MCBs on the same DIN-rail footprint, but the 5SJ4 series uses combined screw-clamp terminals while the 5SY series may differ in terminal type and torque. Check the terminal compatibility on your existing busbars and ring lugs before swapping — the physical rail fit is identical, but the connection method may require a different ferrule or adapter.

MPN
5SJ4306-8HG41