Skip to main content
Siemens 5SJ4330-7HG41 — 3-Pole MCB (DIN Rail)

Siemens 5SJ4330-7HG41 SENTRON MCB, 3P C-curve, 10 kA

MPN5SJ4330-7HG41
Active

Siemens SENTRON 5SJ4 series, 3-pole miniature circuit breaker, C-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC / 60 V DC, 3 MW, DIN rail, IP20/IP40.

$132.08Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4330-7HG41 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SJ4330-7HG41 — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-215 kA
Overvoltage category3
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
5SJ4330-7HG41 — Electrical
ParameterValue
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)3.4 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
5SJ4330-7HG41 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodon standard mounting rail
SealableYes
Accepts supplementary devicesYes
5SJ4330-7HG41 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Vibration resistance (IEC 60068-2-6)±1 mm at 5 to 25 Hz; 50 m/s² at 25 to 150 Hz

Product details

The Siemens 5SJ4330-7HG41 is a SENTRON 5SJ4 series 3-pole miniature circuit breaker with C-curve tripping characteristic, rated 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. It also carries a 60 V DC rating, so it can protect DC control circuits or small battery-backed loads, not just AC branch circuits. Snaps onto standard DIN rail (35 mm) and takes up 3 modular width units (54 mm wide, 70 mm deep, 110 mm tall).

Construction notes

Sealable (can be locked in OFF position with a padlock) for lockout/tagout compliance. Vibration tested to 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz (4 s), so it holds up on machine-mounted subpanels near motors or conveyors. Rated for mechanical engineering and industry environments per the manufacturer's suitability classification. EMC environment B (immunity not applicable) — this is a passive protective device, not a controller, so no radiated-immunity testing applies.

Frequently asked questions

Where can I buy 5SJ4330-7HG41 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm quote.

What is the breaking capacity of 5SJ4330-7HG41?

10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. The IEC 60947-2 figure is the one to use for industrial feeder protection where fault currents are higher.

What is the C-curve tripping characteristic?

C-curve trips at 5–10 times rated current, designed for moderate inrush loads like small motors, transformers, and lighting banks. It's the standard choice for general industrial branch circuits.

Does 5SJ4330-7HG41 fit on DIN rail?

Yes, it snaps onto standard 35 mm mounting rail. Width is 54 mm (3 modular units), depth 70 mm, height 110 mm. Mounting position is any.

MPN
5SJ4330-7HG41