Skip to main content
Siemens 5SJ6110-6 — 1-Pole MCB (DIN Rail)

5SJ6110-6 SENTRON MCB, 1-pole B 10A, 6kA

MPN5SJ6110-6

Siemens SENTRON 5SJ6, miniature circuit breaker, 1-pole B-curve 10 A, 6 kA breaking capacity, 240 V AC, 18 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ6110-6 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
5SJ6110-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage category3
5SJ6110-6 — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ6110-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SJ6110-6 is a 1-pole miniature circuit breaker from the SENTRON 5SJ6 family, rated 10 A with a B-curve tripping characteristic and a 6 kA breaking capacity per EN 60898 and IEC 60947-2. It snaps onto a DIN rail in any mounting position, occupying one modular width unit (18 mm wide, 76 mm deep, 90 mm tall).

Rated 240 V AC single-phase, with an insulation voltage of 440 V AC and a multi-phase maximum of 440 V AC. The 6 kA breaking capacity at 230/400 V per EN 60898 is the standard domestic and light commercial fault current rating — adequate for most distribution boards where the prospective short-circuit current at the main switch is below that threshold. The DC rating is 60 V, so it can also protect a 48 V DC control circuit or a small solar string, but verify polarity and arc extinction for DC use. Operational current is 10 A at AC. The mechanical service life is 20 000 switching cycles typical. Ambient temperature range is -40 °C to +75 °C, with periodic exposure to +55 °C and 95% humidity — wide enough for unheated enclosures in northern climates or hot attics. Touch protection is built in (IP20 with connected conductors).

Frequently asked questions

Where can I buy 5SJ6110-6 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What is the difference between 5SJ6110-6 and 5SJ6220-6?

The 5SJ6220-6 is a 2-pole version of the same SENTRON 5SJ6 platform. The 5SJ6110-6 is 1-pole, 18 mm wide; the 5SJ6220-6 occupies 36 mm (2 modules). Both share the B-curve, 10 A rating, and 6 kA breaking capacity. A panel designed for the 2-pole unit cannot accept the 1-pole without rewiring the busbar and freeing a module space.

What compliance documentation does Siemens provide for 5SJ6110-6?

Siemens SENTRON 5SJ6 breakers carry IEC 60898 and IEC 60947-2 ratings, CE marking for the European market, and are designed for installation per EN 61439 low-voltage switchgear standards. Specific RoHS, REACH, and UL documentation is available from Siemens on request; the part is halogen-free and silicon-free as standard.

MPN
5SJ6110-6