Skip to main content
Siemens 5SJ6110-7 — 1-Pole MCB (DIN Rail)

Siemens 5SJ6110-7 SENTRON MCB, 1-Pole C 10A 6kA

MPN5SJ6110-7

Siemens SENTRON 5SJ6 miniature circuit breaker, 1-pole, C-curve, 10 A rated, 6 kA breaking capacity per EN 60898, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ6110-7 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
5SJ6110-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Overvoltage category3
5SJ6110-7 — Mounting & Connection
ParameterValue
Mounting positionany
Installation depth70 mm
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ6110-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SJ6110-7 is a 1-pole SENTRON 5SJ6 miniature circuit breaker rated 10 A with a C tripping characteristic, breaking 6 kA per EN 60898 and IEC 60947-2 at 240 V AC.

Mounts in any position; supply cord can enter from either end. Rated IP20 with conductors connected, meaning it's intended for enclosed panels, not wet or dusty environments.

Electrical ratings and environment

Rated for AC/DC operation: 240 V AC single-phase or up to 60 V DC maximum. Insulation voltage is 440 V AC, and overvoltage category 3 means it's built for fixed-installation distribution panels where surges are expected. Energy limiting class 3 keeps let-through energy low, reducing stress on downstream equipment. Vibration resistance tested to 50 m/s² at 25–150 Hz and 60 m/s² at 10–150 Hz per IEC 60068-2-6 — good for industrial panels near rotating machinery. Mechanical life is 20 000 switching cycles typical.

Environmental and compliance details

Halogen-free and silicon-free construction — important for environments where outgassing can contaminate sensitive contacts or optics. Operating temperature range -40 to 75 °C, with periodic exposure to +55 °C and 95% humidity. Sealable cover and touch protection are standard. Degree of pollution 2 (non-conductive, occasional condensation).

Frequently asked questions

What are the key ratings of 5SJ6110-7?

1-pole, C-curve, 10 A rated current, 6 kA breaking capacity per EN 60898 and IEC 60947-2 at 240 V AC, 60 V DC max, 70 mm depth, 1 width unit.

Where can I buy 5SJ6110-7?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 5SJ6110-7 drop into a panel specified for 5SJ6216-6?

Not directly — 5SJ6216-6 is a 2-pole, 16 A, B-curve breaker occupying 2 width units. The 5SJ6110-7 is 1-pole, 10 A, C-curve, 1 width unit. Same 70 mm depth and DIN-rail mount, but the pole count and trip curve differ; you'd need to rewire the circuit and possibly adjust the panel layout.