Skip to main content
Siemens 5SJ6315-7 — 3-Pole MCB (DIN Rail)

Siemens 5SJ6315-7 SENTRON MCB, C-1.6A, 3P, 6kA

MPN5SJ6315-7

Siemens SENTRON 5SJ6 series, 5SJ6315-7 miniature circuit breaker, 3-pole, C tripping characteristic, 1.6 A rated current, 6 kA breaking capacity per EN 60898, 400 V AC.

$70.89Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ6315-7 — Identification
ParameterValue
Design / model code5SJ6
Brand nameSENTRON
Number of poles3
5SJ6315-7 — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 608986 kA
Breaking capacity per IEC 60947-26 kA
Overvoltage category3
IP protection classIP20, with connected conductors
5SJ6315-7 — Electrical
ParameterValue
Rated frequency50 Hz
5SJ6315-7 — Mechanical
ParameterValue
Mounting positionany
Installation depth70 mm
SealableYes
5SJ6315-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturePeriodically +55°C, max. 95% humidity

Product details

The Siemens SENTRON 5SJ6315-7 is a 3-pole miniature circuit breaker (MCB) from the 5SJ6 series, rated at 1.6 A with a C tripping characteristic. It breaks fault currents up to 6 kA per EN 60898 and IEC 60947-2 at 400 V AC — the standard interrupting rating for branch-circuit protection in commercial and light industrial panels.

The 1.6 A rating is the continuous current it carries without tripping at 40 °C ambient — sized for a small lighting circuit or a control transformer secondary, not a general-purpose receptacle branch. The 6 kA SCCR at 400 V tells you it safely interrupts a bolted fault up to that level without rupturing, which covers most distribution panels fed by a 250 kVA or smaller transformer. The 3-pole configuration switches all three phases simultaneously, so it is the right choice for a three-phase motor branch or a 400 V three-phase lighting circuit.

Panel integration

The MCB snaps onto a standard 35 mm DIN rail and occupies 3 width units (roughly 54 mm). Installation depth is 70 mm, which fits most 80 mm deep enclosures. The terminal accepts solid or stranded conductors from 0.75 mm² up to 25 mm² — enough for the load side wiring on a 1.6 A circuit. Mounting position is any orientation, so it works in vertical or horizontal panel layouts.

Frequently asked questions

What is the breaking capacity of the 5SJ6315-7?

Rated at 6 kA per both EN 60898 and IEC 60947-2 at 400 V AC. That covers most commercial and light industrial distribution panels.

Where can I buy the 5SJ6315-7?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will the 5SJ6315-7 drop into a panel designed for the 5SL4120-7CC?

Not without rewiring — the 5SJ6315-7 is a 3-pole MCB (3 width units), while the 5SL4120-7CC is a 1-pole unit (1 width unit). The footprint and terminal arrangement differ.

MPN
5SJ6315-7