The 6 kA breaking capacity per EN 60898 (also rated 6 kA per IEC 60947-2) tells you it can safely interrupt a fault current up to 6,000 A at 400 V without welding contacts or cascading damage upstream. The 3-pole design (3 width units, 70 mm installation depth) fits standard DIN-rail enclosures.
Deployment context
The 70 mm installation depth fits flush in most 100 mm deep enclosures. Rated for ambient temperatures from -20 to +45 °C, with periodic excursions to +55 °C at up to 95% humidity — suitable for unconditioned electrical rooms and outdoor-rated cabinets within that range. Vibration resistance tested to 50 m/s² at 25 to 150 Hz and 60 m/s² at 10 to 150 Hz per IEC 60068-2-6, so it holds up on machine-mounted panels near rotating equipment.