Skip to main content
Siemens 5SJ6413-7 — 4-Pole MCB (DIN Rail)

Siemens 5SJ6413-7 SENTRON MCB, 4-Pole C 13A 6kA

MPN5SJ6413-7

Siemens SENTRON 5SJ6 series, miniature circuit breaker, 4-pole, C tripping characteristic, 13 A rated current, 6 kA breaking capacity, 400 V AC, 70 mm installation depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ6413-7 — Identification
ParameterValue
Type / order code5SJ6
Brand nameSENTRON
5SJ6413-7 — Ratings
ParameterValue
Number of poles4
Pole configuration4
Rated current (In), AC13 A
Rated voltage, DC (max.)60 V
Voltage typeAC/DC
Rated frequency50 Hz
5SJ6413-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 608986 kA
Rated breaking capacity, per IEC 60947-26 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SJ6413-7 — Mechanical
ParameterValue
Width in modular units4
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SJ6413-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity
5SJ6413-7 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)20 000

Product details

Siemens 5SJ6413-7 — 4-pole C-curve MCB at 13 A

The Siemens 5SJ6413-7 is a SENTRON miniature circuit breaker with four poles, a C tripping characteristic, and a 13 A rated current at 400 V AC. It breaks fault currents up to 6 kA per EN 60898 and IEC 60947-2, which covers most commercial and light industrial panel feeders.

The 6 kA breaking capacity (both EN 60898 and IEC 60947-2) tells you this breaker can safely interrupt a fault up to that level without welding contacts or cascading upstream — standard for sub-distribution boards where the prospective short-circuit current is known to stay under 6 kA. The 440 V insulation voltage and 400 V rated supply voltage confirm it handles 3-phase 400 V line-to-line without derating. Four poles in four width units means it occupies a standard 72 mm on the DIN rail (18 mm per module) — same footprint as any 4-pole 5SJ6. The C characteristic is the middle ground between B (lighting/resistive) and D (high-inrush transformers); for a 13 A motor feeder, it avoids nuisance trips on start-up while still clearing fast on a hard short.

Frequently asked questions

What is the maximum operating temperature for 5SJ6413-7?

The maximum ambient temperature is listed as 75 °C. The minimum is -40 °C. The surrounding temperature influence is periodically up to +55 °C with max. 95% humidity. These limits govern the breaker's thermal-magnetic trip performance — derating may apply above 40 °C.

MPN
5SJ6413-7