Skip to main content
Siemens 5SJ6432-7 — 4-Pole MCB (DIN Rail)

Siemens 5SJ6432-7 SENTRON MCB, 4P C 32A 6kA 400V

MPN5SJ6432-7

Siemens SENTRON 5SJ6 series, miniature circuit breaker 5SJ6432-7, 4-pole, C-curve, 32 A, 6 kA, 400 V AC, 70 mm installation depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ6432-7 — Identification
ParameterValue
Type / order code5SJ6
Brand nameSENTRON
5SJ6432-7 — Ratings
ParameterValue
Number of poles4
Pole configuration4
Rated current (In), AC32 A
Rated voltage, DC (max.)60 V
Voltage typeAC/DC
Rated frequency50 Hz
5SJ6432-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 608986 kA
Rated breaking capacity, per IEC 60947-26 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SJ6432-7 — Mechanical
ParameterValue
Width in modular units4
Installation depth70 mm
Mounting positionany
SealableYes
5SJ6432-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity
5SJ6432-7 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)20 000

Product details

What this SENTRON 5SJ6432-7 does in the panel

The Siemens 5SJ6432-7 is a 4-pole miniature circuit breaker from the SENTRON 5SJ6 series, rated 32 A at 400 V AC with a C tripping characteristic. Four poles in a single 70 mm-deep module occupy 4 width units on the DIN rail; the any-position mounting and IP20 (with conductors connected) fit standard enclosure layouts.

C-curve means the magnetic trip activates between 5 and 10 times rated current (160–320 A), so it holds through the starting surge of a 7.5 kW motor but clears a bolted fault in under 10 ms. Ambient temperature range –20 to +45 °C; above 45 °C the thermal trip element shifts — derate per the manufacturer's curve if the enclosure runs hot. The sealable feature (yes) allows a lead seal or wire lock through the toggle to prevent unauthorized switching — useful for safety-isolation points or rental-metered circuits.

Depth of 70 mm leaves clearance for wiring ducts and gland plates in a 200 mm-deep enclosure. Overvoltage category 3 suits fixed-installation distribution boards. Vibration resistance rated at 50 m/s² from 25 to 150 Hz and 60 m/s² from 10 to 150 Hz per IEC 60068-2-6 — holds calibration on machine-tool or conveyor panels subject to continuous vibration. Mechanical endurance of 20 000 switching cycles typical for the class.

Frequently asked questions

Where can I buy the 5SJ6432-7?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of the 5SJ6432-7?

6 kA per both EN 60898 and IEC 60947-2, sufficient for most commercial and light industrial distribution boards.

MPN
5SJ6432-7