Skip to main content
Siemens 5SJ6450-6 — 4-Pole MCB (DIN Rail)

Siemens 5SJ6450-6 SENTRON MCB, 4-Pole, B Curve, 50 A, 6 kA

MPN5SJ6450-6

Siemens SENTRON 5SJ6 series, miniature circuit breaker, 4-pole, B characteristic, 50 A rated current, 6 kA breaking capacity, 400 V AC, IP20 with connected conductors.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ6450-6 — Identification
ParameterValue
Type / order code5SJ6
Brand nameSENTRON
5SJ6450-6 — Ratings
ParameterValue
Number of poles4
Pole configuration4
Rated current (In), AC50 A
Rated voltage, DC (max.)60 V
Voltage typeAC/DC
Rated frequency50 Hz
5SJ6450-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Rated breaking capacity (Icn), per EN 608986 kA
Rated breaking capacity, per IEC 60947-26 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SJ6450-6 — Mechanical
ParameterValue
Width in modular units4
Installation depth70 mm
Mounting positionany
SealableYes
5SJ6450-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity
5SJ6450-6 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)20 000

Product details

The Siemens 5SJ6450-6 is a SENTRON 5SJ6 miniature circuit breaker with a B tripping characteristic, rated 50 A at 400 V AC across four poles. It provides 6 kA breaking capacity per both EN 60898 and IEC 60947-2, which means it safely clears faults up to that level on a 400 V distribution board without cascading upstream.

Occupies 4 width units (roughly 72 mm) on a DIN rail; installation depth is 70 mm. The terminals accept solid or stranded conductors from 0.75 mm² up to 25 mm², which covers standard panel wiring up to 4 AWG. Mounting position is unrestricted, so it can go sideways or inverted if the gland plate layout demands it.

Mechanical endurance and approvals

Rated for 20 000 mechanical switching cycles typical. Vibration resistance tested to 50 m/s² at 25-150 Hz and 60 m/s² at 10-150 Hz per IEC 60068-2-6. Overvoltage category 3, insulation voltage 440 V AC. The 5SJ6 series carries EN 60898 and IEC 60947-2 ratings, giving it acceptance across European and international distribution panels. Touch protection is built in on the terminals.

Frequently asked questions

Where can I buy the 5SJ6450-6 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request for a firm price and lead time.

Will the 5SJ6450-6 drop into a panel specified for the 5SJ6220-6?

Not without rewiring — the 5SJ6450-6 is a 4-pole breaker occupying 4 width units, while the 5SJ6220-6 is a 2-pole breaker on 2 width units. The terminal wire range (0.75-25 mm²) and installation depth (70 mm) are the same, so the physical connection method matches, but the pole count and rail footprint differ.

What compliance documentation does Siemens provide for the 5SJ6450-6?

The 5SJ6 series is rated to EN 60898 and IEC 60947-2, and the part is halogen-free and silicon-free. Standard Siemens documentation includes a declaration of conformity for the applicable EU directives; specific RoHS/REACH declarations are available from Siemens upon request or through their product documentation portal.

MPN