The 90 mm height fits standard distribution board cutouts. IP20 with connected conductors — finger-safe on the front, but the busbar area needs clearance from live parts. Mounting position is unrestricted, so it can be installed horizontally or vertically without derating the thermal trip.
Thermal derating and service conditions
Rated 10 A at 30 °C ambient; at 40 °C the continuous current must be limited to 9.24 A, and at 45 °C to 8.8 A.
Material and compliance notes
Sealable per the manufacturer's definition, meaning the breaker can be locked in the OFF position with a standard padlock hasp for lockout/tagout.