Part identity and ratings
Acceptable in any mounting position, which simplifies layout in tight enclosures where vertical or horizontal orientation is constrained.
Electrical and environmental limits
Rated for AC/DC operation: on DC circuits the maximum voltage is 60 V, making it suitable for control-voltage distribution in panels with 24 VDC or 48 VDC supplies. Insulation voltage rated at 440 V AC, with multi-phase operation up to 440 V AC — adequate for 230/400 V three-phase systems where the breaker protects a single-phase branch. Storage temperature range from -40 °C to +75 °C covers most unheated warehouses and transport conditions; the operating ambient is limited to 45 °C (per the 5SJ6 family spec), with periodic humidity up to 95% at 55 °C. Vibration resistance tested to IEC 60068-2-6 at 50 m/s² (25–150 Hz) and 60 m/s² (10–150 Hz), so it holds up in panels mounted on pumps, compressors, or conveyor drives.