Skip to main content
Siemens 5SJ6525-7 — 1-Pole MCB (DIN Rail)

Siemens 5SJ6525-7 SENTRON MCB, 1P+N, C-curve, 25 A, 6 kA

MPN5SJ6525-7

Siemens SENTRON 5SJ6 series, miniature circuit breaker, 1P+N, C-curve, 25 A, 6 kA breaking capacity per EN 60898, 240 V AC, 2 MW units, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ6525-7 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles2
5SJ6525-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage category3
5SJ6525-7 — Mounting & Connection
ParameterValue
Mounting positionany
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ6525-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Rated 25 A at 240 V AC with a 6 kA breaking capacity per EN 60898 (and matching 6 kA per IEC 60947-2), it fits residential, commercial, and light-industrial panels where the prospective short-circuit current stays under 6 kA.

Physical fit and mounting

This is a 1P+N (single-pole switched neutral) MCB occupying 2 modular width units (18 mm each) on a DIN rail. Touch protection is built in per the product feature. Sealable terminals allow the panel builder to lock the cover after commissioning.

Vibration resistance is rated at 50 m/s² from 25 to 150 Hz and 60 m/s² from 10 to 150 Hz per IEC 60068-2-6 — acceptable for most industrial panels but not for direct mounting on high-vibration machinery without additional damping.

Frequently asked questions

What is the breaking capacity of 5SJ6525-7?

6 kA per both EN 60898 and IEC 60947-2, at 240 V AC.

Where can I buy 5SJ6525-7 and get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — no stock or lead-time figures are published here.

Will 5SJ6525-7 drop into a panel specified around 5SJ6220-6?

Both are 2-MW-unit SENTRON 5SJ6 breakers with the same 70 mm depth, DIN-rail mount, and IP20 rating. The key difference is the trip curve: 5SJ6525-7 is C-curve (25 A), while 5SJ6220-6 is B-curve (20 A). If the panel was designed for B-curve coordination, swapping to C-curve may reduce selectivity with upstream devices — verify the coordination study before substituting.

MPN
5SJ6525-7