Skip to main content
Siemens 5SJ6532-7 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SJ6532-7 MCB, 1P+N, C-Curve, 32 A, 6 kA

MPN5SJ6532-7

Siemens SENTRON 5SJ6 series miniature circuit breaker, order code 5SJ6532-7, 1P+N, C tripping characteristic, 32 A rated at 240 V AC, 6 kA breaking capacity per EN 60898.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ6532-7 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles2
5SJ6532-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Overvoltage category3
5SJ6532-7 — Mounting & Connection
ParameterValue
Mounting positionany
Installation depth70 mm
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ6532-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

What this 5SJ6532-7 does in the panel

The Siemens SENTRON 5SJ6532-7 is a 1P+N miniature circuit breaker rated 32 A at 240 V AC, with a C tripping characteristic and 6 kA breaking capacity per EN 60898 (also rated 6 kA per IEC 60947-2). The 1P+N configuration switches the line pole and provides a switched neutral, so the neutral is disconnected when the breaker is off — useful for single-phase final circuits where you want isolation on both conductors. Rated for 440 V insulation voltage and overvoltage category III, it handles the transient environment of a distribution board. The 20 000 mechanical switching cycles give it a solid service life for a panel that sees regular switching, not just fault protection. Pollution degree 2 rating means it's suited for normal industrial or commercial environments with only non-conductive contamination.

Installation and panel fit

Installation depth is 70 mm, and it occupies 2 width units (about 36 mm on a standard rail). The IP20 rating applies with connected conductors; the terminals are touch-protected per the product feature listing. Halogen-free and silicon-free construction means it won't off-gas corrosive compounds in a fire — relevant for panels in critical infrastructure or controlled environments. Sealable with a lead seal for tamper-proofing in metering or rental applications.

Environmental range and compliance

That -40 °C floor matters for unheated electrical rooms or outdoor enclosures in cold climates. The 75 °C ceiling is the internal temperature limit — not the ambient; the breaker itself can withstand that internal temperature without nuisance tripping or damage.

Sourcing and supply posture

For volume procurement or scheduled releases, a blanket order with fixed pricing can be structured.

Frequently asked questions

What is the 5SJ6532-7 rated for?

Rated 32 A at 240 V AC, C-curve, 6 kA breaking capacity per EN 60898 and IEC 60947-2. 1P+N poles, 70 mm installation depth, IP20 with connected conductors.

Where can I buy the 5SJ6532-7?

The 5SJ6532-7 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the difference between 5SJ6532-7 and 5SL4120-7CC?

The 5SL4120-7CC is a 1-pole, 20 A, C-curve MCB with 10 kA breaking capacity, compared to the 5SJ6532-7's 1P+N, 32 A, 6 kA rating. The 5SL4120-7CC switches line only (no switched neutral), while the 5SJ6532-7 provides a switched neutral for single-phase isolation.

MPN
5SJ6532-7