Skip to main content
Siemens 5SL1101-7MB — 1-Pole MCB (DIN Rail)

Siemens 5SL1101-7MB SENTRON MCB, 1A C-Curve 1-Pole 230V

MPN5SL1101-7MB

Siemens SENTRON 5SL1101-7MB miniature circuit breaker, 1-pole, C-curve, 1 A rated current, 230/400 V AC, 3 kA breaking capacity per IEC 60947-2, 1 MW unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL1101-7MB — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL1101-7MB — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SL1101-7MB — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL1101-7MB — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

What it is and what it does

The Siemens 5SL1101-7MB is a SENTRON miniature circuit breaker (MCB) with a C tripping characteristic, rated 1 A at 230 V AC single-phase and 400 V AC multi-phase. It protects branch circuits in residential and light commercial panels against overloads and short circuits, with a breaking capacity of 3 kA per IEC 60947-2.

What the ratings mean for fit

The C-curve trips between 5 and 10 times rated current, so at 1 A it holds through motor inrush and capacitive loads that would nuisance-trip a B-curve, but clears faster than a D-curve on a hard short. The 3 kA breaking capacity per IEC 60947-2 is the industrial rating — sufficient for most sub-distribution boards fed by a transformer, but verify against the prospective short-circuit current at the installation point. The 1-pole, 18 mm wide form factor occupies one modular unit on a DIN rail, matching the standard SENTRON panel layout.

Panel integration

Snap-on mounting to 35 mm DIN rail per EN 60715, with any mounting position allowed. Depth of 76 mm and installation depth of 70 mm clear standard gland plates and busbar systems. The IP20 rating with connected conductors means it is protected against finger contact but not washdown — suitable for dry indoor enclosures only.

Frequently asked questions

Where can I buy the 5SL1101-7MB and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Siemens provide for the 5SL1101-7MB?

The product is designed to IEC 60947-2 and EN 60898 standards. It is halogen-free and silicon-free. Specific RoHS, REACH, and UL documentation should be requested at quote time as part of the RFQ package.

MPN