Skip to main content
Siemens 5SL1106-7MB — 1-Pole MCB (DIN Rail)

Siemens 5SL1106-7MB SENTRON MCB, 1P C 6A 3kA

MPN5SL1106-7MB

Siemens SENTRON miniature circuit breaker, 5SL1106-7MB, 1-pole, C-curve, 6 A, 3 kA breaking capacity per IEC 60947-2, 230/400 V AC, 1 MWU.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SL1106-7MB — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL1106-7MB — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SL1106-7MB — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL1106-7MB — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SL1106-7MB SENTRON MCB – 1-pole, C-curve, 6 A

The Siemens 5SL1106-7MB is a SENTRON miniature circuit breaker (MCB) with a single pole, C-trip characteristic, and a 6 A rated current. It breaks fault currents up to 3 kA per IEC 60947-2 at 230/400 V AC, 50/60 Hz. That 3 kA rating means it is sized for residential and light commercial sub-distribution where the prospective short-circuit current stays under that threshold — not for high-fault industrial mains where a 10 kA or higher unit would be required. The C-curve (5–10× In) handles moderate inrush from small motors, transformers, or capacitive loads without nuisance tripping. Occupying a single modular width unit (18 mm) on a DIN rail, it snaps into standard distribution boards. The IP20 rating (with connected conductors) is typical for enclosed panel use — no washdown or outdoor exposure. Halogen-free and silicon-free construction matters for installations where off-gassing or silicone contamination must be avoided, such as in clean rooms or sealed enclosures.

Integration notes

Mounts in any position on a standard DIN rail. The 76 mm depth and 70 mm installation depth fit typical consumer-unit and sub-distribution enclosures. The sealable design allows the installer to lock the toggle position after commissioning — useful for tamper-proofing in shared or public-access panels. Overvoltage category III and pollution degree 2 align with fixed-installation requirements per IEC 60947-2.

Frequently asked questions

What is the breaking capacity of 5SL1106-7MB?

The breaking capacity is 3 kA per IEC 60947-2 at 230/400 V AC.

Where can I buy 5SL1106-7MB?

The 5SL1106-7MB is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Will 5SL1106-7MB drop into a panel specified around 5SL4363-7?

No — the 5SL4363-7 is a 3-pole, 3-module-width unit (54 mm) with a 10 kA breaking capacity, so it occupies three times the DIN space and requires a higher-fault-rated bus. The 5SL1106-7MB is a single-pole, 18 mm wide unit rated 3 kA; it fits only single-pole positions in a panel designed for the 5SL4363-7.

MPN
5SL1106-7MB