It breaks fault currents up to 3 kA per IEC 60947-2 at 230/400 V AC, 50/60 Hz. It is not intended for motor-starting duty where higher inrush would nuisance-trip a B-curve device.
Fit and footprint
Mounting position is unrestricted. The IP20 rating applies only with conductors connected — meaning the terminals are finger-safe once wired, but the breaker itself is not sealed against dust ingress in an unpopulated panel. Sealable design allows a lockout tagout hasp on the toggle.
Electrical environment
The single-pole unit switches the line conductor only; neutral must be bonded separately. Power dissipation is 3.1 W per pole at rated current — negligible for a single unit but worth summing in a densely populated sub-distribution board.