Specifications

5SL1325-7MB — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL1325-7MB — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per IEC 60947-23 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree2
5SL1325-7MB — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)2.9 W
Mechanical service life (operating cycles, typ.)4 000
Rated voltage (AC, single-phase)253 V
5SL1325-7MB — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
5SL1325-7MB — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

What it is and what the ratings mean for fit

The Siemens 5SL1325-7MB is a 3-pole SENTRON miniature circuit breaker with a C-tripping characteristic, rated 25 A at 230/440 V AC, 50/60 Hz. The C-curve (5–10× In magnetic trip) means it handles moderate inrush from motor starters and lighting ballasts without nuisance tripping — the standard choice for general-purpose branch circuits in residential and light commercial infrastructure. The 3 kA breaking capacity per IEC 60947-2 defines its fault-interrupt limit; this is not a high-fault panel breaker — it belongs downstream of a higher-rated upstream device in a coordinated distribution board.

Panel fit and integration

Snap-on DIN-rail mount, 3 modular width units (54 mm wide), 90 mm tall, 76 mm deep with 70 mm installation depth. IP20 with conductors connected — standard for enclosed distribution boards. Mounting position any, so it fits vertical or horizontal busbars. Sealable, halogen-free, silicon-free. Overvoltage category III, pollution degree 2. The 2.9 W power loss per pole at rated current matters for thermal derating in a crowded enclosure — check the total dissipation against your panel's thermal budget.

Frequently asked questions

What is the breaking capacity of the 5SL1325-7MB?

3 kA rated value according to IEC 60947-2 at 230/440 V AC.

Where can I buy the 5SL1325-7MB and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.