Skip to main content
Siemens 5SL1332-7MB — 3-Pole MCB (DIN Rail)

Siemens 5SL1332-7MB SENTRON MCB, 3P C-32A, 3kA

MPN5SL1332-7MB

Siemens SENTRON miniature circuit breaker, 5SL1332-7MB, 3-pole, C-curve, 32 A rated, 3 kA breaking capacity per IEC 60947-2, 230/400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL1332-7MB — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL1332-7MB — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per IEC 60947-23 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree2
5SL1332-7MB — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)3.1 W
Mechanical service life (operating cycles, typ.)4 000
Rated voltage (AC, single-phase)253 V
5SL1332-7MB — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
5SL1332-7MB — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

What it is and what it does

The Siemens SENTRON 5SL1332-7MB is a 3-pole miniature circuit breaker (MCB) with a C tripping characteristic, rated 32 A at 230/400 V AC. It breaks fault currents up to 3 kA per IEC 60947-2, which covers the majority of residential and light commercial sub-distribution boards where the prospective short-circuit current stays under that threshold. The C-curve means it trips between 5 and 10 times rated current — standard for general-purpose loads like lighting, socket outlets, and small appliances where inrush isn't extreme.

Panel fit and mounting

Occupies 3 modular width units (54 mm) on a DIN rail. Depth is 76 mm, installation depth 70 mm — standard SENTRON 5SL footprint, so it drops into existing panels without re-drilling gland plates. Mounting position is any; IP20 with conductors connected, suitable for enclosed distribution boards. Sealable design allows lockout-tagout on the toggle.

Environmental and compliance

Halogen-free and silicon-free construction. Rated for ambient temperatures from -40 °C to 75 °C, with overvoltage category III and pollution degree 2 — covers the typical range for indoor panel environments. Power loss per pole is 3.1 W at rated current in hot operating state; factor that into enclosure thermal calculations if the board is densely populated.

Frequently asked questions

Where can I buy the 5SL1332-7MB and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is the breaking capacity of the 5SL1332-7MB?

Rated 3 kA according to IEC 60947-2 at 230/400 V AC. This is the standard breaking capacity for the 5SL1 series, suitable for sub-distribution where fault levels are moderate.

Will the 5SL1332-7MB fit a panel designed for the 5SL4363-7?

Yes — both share the same 54 mm width (3 modular units), 76 mm depth, and 70 mm installation depth. The 5SL4363-7 carries a higher 10 kA breaking capacity and 10 000 mechanical cycles vs 4 000 on this unit, but the physical footprint is identical. No rewiring or panel modification needed.

MPN
5SL1332-7MB