Mount in any position; the neutral conductor is switched internally, so no separate neutral bar needed for the protected circuit.
Current production and sourcing
Lifecycle stage is current — this is an active, in-production part.
Rated 10 A at 30 °C ambient. Derates to 9.52 A at 40 °C, 9.27 A at 45 °C, 9.01 A at 50 °C, 8.75 A at 55 °C, and 8.48 A at 60 °C. If the panel runs warm, size the circuit accordingly — the 10 A nameplate is only good at 30 °C. Operating humidity limits: 85% rF up to 45 °C, dropping to 43% rF between 45 and 60 °C.
Designed to IEC/EN 60898-1 and GB/T 10963.1. Halogen-free and silicon-free construction. Energy limitation class 3. Suitable for residential buildings and infrastructure per the manufacturer's designation.