Skip to main content
Siemens 5SL3010-7KL — 1-Pole MCB (DIN Rail)

Siemens 5SL3010-7KL SENTRON MCB, 10 A C-Curve, 1P+N

MPN5SL3010-7KL
Active

Siemens SENTRON 5SL3010-7KL miniature circuit breaker, 10 A, C-curve, 1P+N, 4.5 kA per IEC/EN 60898-1, DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3010-7KL — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Pole design1P+N
Application suitabilityResidential buildings/infrastructure
5SL3010-7KL — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL3010-7KL — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodstandard rail
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL3010-7KL — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Mount in any position; the neutral conductor is switched internally, so no separate neutral bar needed for the protected circuit.

Current production and sourcing

Lifecycle stage is current — this is an active, in-production part.

Rated 10 A at 30 °C ambient. Derates to 9.52 A at 40 °C, 9.27 A at 45 °C, 9.01 A at 50 °C, 8.75 A at 55 °C, and 8.48 A at 60 °C. If the panel runs warm, size the circuit accordingly — the 10 A nameplate is only good at 30 °C. Operating humidity limits: 85% rF up to 45 °C, dropping to 43% rF between 45 and 60 °C.

Designed to IEC/EN 60898-1 and GB/T 10963.1. Halogen-free and silicon-free construction. Energy limitation class 3. Suitable for residential buildings and infrastructure per the manufacturer's designation.

Frequently asked questions

How do I get current pricing and availability for 5SL3010-7KL?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

Will 5SL3010-7KL drop into a panel that was specified around 5SY6013-7 without rewiring?

Both are 1-module-width DIN-rail MCBs with similar dimensions (18 mm wide, 76 mm deep), so the 5SL3010-7KL fits the same physical footprint. However, verify the breaking capacity and trip curve match your panel's coordination study — the 5SL3010-7KL carries a 4.5 kA breaking capacity per IEC/EN 60898-1, which may differ from the 5SY6013-7 rating.

What compliance documentation does this brand provide for 5SL3010-7KL (RoHS, REACH, UL, IEC)?

The breaker is designed to IEC/EN 60898-1 and GB/T 10963.1. It is halogen-free and silicon-free. For specific RoHS/REACH declarations and any UL listing, request the manufacturer's compliance documentation at quote time.

MPN