Skip to main content
Siemens 5SL3101-7MB — 1-Pole MCB (DIN Rail)

Siemens 5SL3101-7MB SENTRON MCB, 1A C-Curve 1P 4.5kA

MPN5SL3101-7MB
Active

Siemens SENTRON 5SL3101-7MB miniature circuit breaker, 1-pole, C-curve, 1 A rated, 4.5 kA (EN 60898) / 5 kA (IEC 60947-2), 1 MW unit, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SL3101-7MB — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL3101-7MB — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL3101-7MB — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL3101-7MB — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Siemens SENTRON 5SL3101-7MB — 1 A C-Curve Miniature Circuit Breaker

The Siemens 5SL3101-7MB is a SENTRON miniature circuit breaker rated 1 A with a C-tripping characteristic, 1-pole construction, and a breaking capacity of 4.5 kA per EN 60898 or 5 kA per IEC 60947-2 at 230/400 V AC.

The C-curve trips between 5 and 10 times rated current (5–10 A for this 1 A unit), which suits moderate inrush loads like small transformers or lighting banks where a B-curve would nuisance-trip but a D-curve would be too slow for conductor protection. The 4.5 kA (EN 60898) / 5 kA (IEC 60947-2) breaking capacity covers the vast majority of residential and commercial service-entrance fault levels in 230/400 V networks; if your prospective short-circuit current exceeds 5 kA at the panel, step up to a 6 kA or 10 kA rated sibling like the 5SL6120-7. Mechanical endurance is rated at 20 000 operating cycles typical — above the 10 000 cycles common on many compact MCBs, reflecting the SENTRON series' design for frequent switching in lighting or small motor-disconnect roles where the breaker doubles as a switch.

Snap-on DIN rail mount, 18 mm width (1 MW), 76 mm depth — fits standard distribution board cutouts. The IP20 rating (with conductors connected) means it is intended for enclosed panels, not outdoor or washdown locations. Halogen-free and silicon-free construction supports use in clean-room or high-reliability environments where outgassing must be minimized. The 50/60 Hz frequency range covers both 50 Hz European and 60 Hz North American / Middle Eastern grids, though the voltage ratings (230/400 V single-phase / multi-phase) align with IEC 60364 wiring rules.

Frequently asked questions

Where can I buy the 5SL3101-7MB and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will the 5SL3101-7MB drop into a panel specified for the 5SL6120-7 without rewiring?

Yes — both share the same 18 mm width, 76 mm depth, DIN-rail footprint, and 1-pole form factor. The 5SL6120-7 has a higher breaking capacity (6 kA vs 4.5 kA per EN 60898) and a higher current rating (20 A vs 1 A), so it is not a direct functional substitute for the 1 A circuit, but the mechanical fit is identical.

What compliance documentation does Siemens provide for the 5SL3101-7MB?

The part carries IEC 60898 and IEC 60947-2 ratings, is halogen-free and silicon-free, and is designed for overvoltage category III / pollution degree 2. Standard Siemens SENTRON documentation includes a CE declaration of conformity and manufacturer test certificates; specific RoHS/REACH declarations are available on request.

MPN
5SL3101-7MB