Siemens SENTRON 5SL3105-7 — 1-pole C-curve MCB, 0.5 A
It breaks 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — the IEC figure is the one that governs industrial panel coordination, since it tests at the higher prospective fault current typical of distribution boards. The C-curve (5–10× In) means it holds through motor inrush and transformer magnetizing peaks without nuisance tripping, so it suits mixed resistive-inductive loads in residential infrastructure and light commercial sub-distribution.
Mounting position any, so it fits vertical or horizontal busbars without derating the 0.9 W per-pole power loss. Sealable housing; halogen-free and silicon-free construction for environments sensitive to outgassing (clean rooms, food processing zones).