Siemens 5SL3110-7 — 1-Pole MCB (DIN Rail)

Siemens 5SL3110-7 SENTRON MCB, 1P C 10A, 4.5kA

MPN5SL3110-7

Siemens SENTRON 5SL3110-7 miniature circuit breaker, 1-pole, C-curve, 10 A, 230/400 V AC, 4.5 kA per EN 60898, 1 MWU wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SL3110-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL3110-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL3110-7 — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL3110-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL3110-7 is a SENTRON miniature circuit breaker, 1-pole, C-curve, rated 10 A at 230/400 V AC. It breaks 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — enough for residential and light commercial distribution boards where the prospective fault current stays under that ceiling.

C-curve trips between 5× and 10× In (50–100 A for this 10 A unit). That suits mixed loads with moderate inrush — lighting banks, small transformers, contactor coils — where a B-curve would nuisance-trip on startup but a D-curve would let a sustained overload run too long. The 4.5 kA breaking capacity per EN 60898 is the standard domestic rating; the 5 kA per IEC 60947-2 gives a small margin for industrial panel coordination. If your distribution board's SCCR exceeds 5 kA, step up to the 5SL series' 10 kA variants. Single-pole switching, 250 V phase-to-neutral or 400 V phase-to-phase (single-phase operation). Rated for 50/60 Hz supply. The 72 V DC maximum means it can also protect DC control circuits — common in 48 V or 60 V telecom/battery-backed loads — but verify polarity and arc extinction for DC use.

Occupies 1 modular width unit (18 mm) on standard DIN rail. IP20 with connected conductors, so it belongs inside a panel, not exposed to washdown. Sealable, halogen-free, silicon-free — relevant for clean-room or food-bev zones where outgassing or contamination is a concern.

Frequently asked questions

What is the breaking capacity of 5SL3110-7?

4.5 kA per EN 60898 and 5 kA per IEC 60947-2. The EN rating is the domestic standard; the IEC rating gives a small margin for industrial panel coordination.

Will 5SL3110-7 drop into a panel specified for 5SL4363-7?

No — 5SL4363-7 is a 3-pole unit (54 mm wide, 3 MWU) with a 10 kA breaking capacity. The 5SL3110-7 is 1-pole (18 mm wide, 1 MWU) at 4.5 kA. They share the same depth (76 mm) and mounting rail, but the pole count and fault rating differ. You would need to rewire the circuit and possibly the busbar.

Where can I buy 5SL3110-7?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
5SL3110-7