SENTRON 5SL3120-6 — 1-pole B-curve MCB, 20 A
It breaks faults up to 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 at 400 V AC — enough for residential and light commercial distribution boards where the prospective short-circuit current stays under those thresholds. Not the right choice for motor circuits with high starting current; that calls for a C or D curve. At 40 °C ambient the continuous rating derates to 18.79 A, and at 55 °C it drops to 16.8 A.
Snap-on DIN rail mount, 1 modular unit wide (18 mm). Sealable design and touch protection are built in.