Skip to main content
Siemens 5SL3132-7 — 1-Pole MCB (DIN Rail)

Siemens 5SL3132-7 SENTRON MCB, 1P C 32A, 4.5kA

MPN5SL3132-7

Siemens SENTRON 5SL3132-7, 1-pole miniature circuit breaker, C-curve, 32 A rated at 400 V AC, 4.5 kA breaking capacity per EN 60898, 1 MW width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3132-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityResidential buildings/infrastructure
5SL3132-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)4.5 kA
Energy limitation class3
Overvoltage categoryIII
5SL3132-7 — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL3132-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

It carries a C tripping characteristic — meaning it holds through moderate inrush (5–10× rated current) before opening — and is rated 32 A at 400 V AC per EN 60898, with a 4.5 kA breaking capacity certified to both EN 60898 and IEC 60947-2.

At 40 °C the breaker derates to 30.06 A, and at 45 °C to 28.8 A. At 55 °C it carries 26.89 A. The C-curve is standard for general-purpose loads like lighting, socket circuits, and small appliances; it tolerates the brief inrush of a motor or capacitor bank better than a B-curve would. It mounts in any position and is rated IP20 with connected conductors — suitable for dry indoor enclosures only, not washdown or outdoor exposure. For DC applications, the maximum rated voltage is 72 V — so it can protect a 48 V or 60 V DC bus, but not a 110 V DC control circuit. The breaker does not switch the neutral conductor (1P only).

Frequently asked questions

What is the breaking capacity of the 5SL3132-7?

The breaking capacity is 4.5 kA per both EN 60898 and IEC 60947-2 at 400 V AC. That is the maximum prospective fault current it can safely interrupt.

What is the C-curve tripping characteristic for?

The C-curve trips at 5–10 times rated current, making it suitable for general-purpose loads like lighting, socket outlets, and small appliances that have moderate inrush. It is not intended for high-inrush loads like large motors or transformers.

Can the 5SL3132-7 be used on DC circuits?

Yes, but only up to 72 V DC maximum. It is not rated for higher DC voltages such as 110 V DC control circuits.

Where can I buy the 5SL3132-7?

The 5SL3132-7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.