Siemens 5SL3204-7MB — 2-Pole MCB (DIN Rail)

Siemens 5SL3204-7MB SENTRON MCB, 2P C 4A 4.5kA

MPN5SL3204-7MB
Active

Siemens SENTRON 5SL3204-7MB miniature circuit breaker, 2-pole, C-curve, 4 A, 4.5 kA breaking capacity per EN 60898 at 400 V AC, 2 MW units wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3204-7MB — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentResidential buildings/infrastructure
5SL3204-7MB — Electrical
ParameterValue
Number of poles2
Supply voltage at AC rated value400 V
5SL3204-7MB — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SL3204-7MB — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SL3204-7MB — Environmental
ParameterValue
Pollution degree2
At 30 °C rated value4 A
5SL3204-7MB — Specifications
ParameterValue
At AC rated value4 A
According to EN 60898 rated value4.5 kA
With single-phase operation at AC rated value250 V
Energy Limitation Class3

Product details

The Siemens 5SL3204-7MB is a SENTRON miniature circuit breaker (MCB) — a 2-pole, C-curve device rated 4 A with a 4.5 kA breaking capacity at 400 V AC per EN 60898.

The 4 A rating (at 30 °C, per) governs the continuous load current — wire this into a circuit drawing over 3.2 A continuous and the thermal trip will eventually open. The C-curve means magnetic trip occurs at 5–10× In (20–40 A), so it passes brief motor-start surges but clears a hard short fast. Breaking capacity of 4.5 kA at 400 V AC (per EN 60898) means it can safely interrupt a fault current up to 4.5 kA without welding contacts or rupturing the case. For installations where the prospective short-circuit current exceeds that, step up to the 5SL4 series (10 kA) or add a current-limiting upstream device. Two poles, two modular-width units (36 mm wide, per and). That's the DIN-rail footprint: it occupies two adjacent 18 mm slots in a distribution board. Depth is 76 mm with 70 mm installation depth — verify gland-plate clearance if the enclosure is shallow.

Rated for overvoltage category III (, degree of pollution 2), which covers fixed-installation distribution boards downstream of the main service entrance.

Frequently asked questions

Where can I buy 5SL3204-7MB and get a price?

Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not from a static listing.

What is the difference between 5SL3204-7MB and 5SL4363-7?

The 5SL4363-7 is a 3-pole, 63 A, C-curve MCB with a 10 kA breaking capacity (per EN 60898 and IEC 60947-2). The 5SL3204-7MB is 2-pole, 4 A, 4.5 kA. They share the same 76 mm depth and 90 mm height, but the 5SL4363-7 is 54 mm wide (3 MW) vs 36 mm (2 MW) for the 4 A unit. They are not drop-in interchangeable — the pole count, rating, and breaking capacity are different.

What compliance documentation does Siemens provide for 5SL3204-7MB?

The 5SL3204-7MB is certified to EN 60898 (breaking capacity of 4.5 kA at 400 V AC). It is halogen-free and silicon-free. Standard Siemens documentation includes CE declaration of conformity and, where applicable, UKCA. RoHS and REACH compliance data is available through Siemens Industry Online Support.