It breaks fault currents up to 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — the EN rating governs residential and commercial final circuits, while the IEC rating applies to industrial panelboard applications where the breaker is part of a larger assembly. The 2-pole design switches both phase and neutral in a single module width of 36 mm (2 MW).
Installation depth 70 mm, overall depth 76 mm. Sealable with a lockable cover (sealable = yes) for tamper-proof isolation in public-access panels.