It's built for residential and infrastructure panels — think lighting, socket circuits, and general-purpose branch protection in a DIN-rail enclosure.
The B curve means the magnetic trip activates at 3 to 5 times rated current (75–125 A for this 25 A unit), so it's a good fit for resistive and general-purpose loads where inrush isn't severe — lighting, small transformers, control circuits. Rated 400 V AC phase-to-phase, with a maximum of 440 V in multi-phase operation. The 2-pole configuration switches both live conductors but does not switch the neutral — verify your circuit's neutral switching requirement before specifying. Terminal torque spec is 2.5 to 3 N·m, and the screw terminals accept solid or stranded conductors from 0.75 to 25 mm².