Panel-builder commissioning notes
Rated breaking capacity is 4.5 kA per both IEC 60898 and IEC 60947-2, which covers most low-fault-level distribution boards.
At 40 °C the continuous current derates to 3.81 A, at 45 °C to 3.68 A, and at 55 °C to 3.5 A.
It is sealable and features touch protection. The product is classified per IEC 81346-2 and DIN EN 61346-2 as function code F. The neutral conductor is not switched (3P, no switched neutral). Energy limitation class is 3, indicating a moderate let-through energy level for coordination with downstream devices.