Skip to main content
Siemens 5SL3332-6 — 3-Pole MCB (DIN Rail)

Siemens 5SL3332-6 SENTRON MCB, 3P, B-Char, 32 A, 4.5 kA

MPN5SL3332-6

Siemens SENTRON 5SL3332-6, 3-pole miniature circuit breaker, B characteristic, 32 A, 4.5 kA breaking capacity, 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3332-6 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Suitability for operationResidential buildings/infrastructure
5SL3332-6 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 608984.5 kA
Breaking capacity per IEC 60947-24.5 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL3332-6 — Electrical
ParameterValue
Rated current (AC)32 A
Rated voltage (AC, multi-phase)440 V
5SL3332-6 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
5SL3332-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturePeriodically +55°C, max. 95% humidity

Product details

Panel-builder commissioning note

The Siemens 5SL3332-6 is a 3-pole SENTRON miniature circuit breaker with B tripping characteristic, rated 32 A at 400 V AC and a breaking capacity of 4.5 kA per IEC 60898 and IEC 60947-2.

Snap-on DIN-rail mount, any position. Accepts up to 440 V AC multi-phase. No neutral conductor switching — this is a straight 3-pole overcurrent device. Suitable for residential buildings and infrastructure applications.

Frequently asked questions

What is the breaking capacity of 5SL3332-6?

The 5SL3332-6 is rated 4.5 kA breaking capacity per both IEC 60898 and IEC 60947-2 at 400 V AC.

What is the temperature range for 5SL3332-6?

Operating ambient temperature range is -40 °C to 75 °C, with derated current at elevated temperatures (30.45 A at 40 °C, 29.76 A at 45 °C, 27.97 A at 55 °C).

Will 5SL3332-6 drop into a panel specified around 5SL4120-7CC without rewiring?

The 5SL3332-6 is a 3-pole B-characteristic 32 A MCB; the 5SL4120-7CC is a different pole/current variant. Both share the same 5SL DIN-rail footprint and modular width per pole, so mechanical fit is identical — but verify the rating and characteristic match your circuit design before substitution.

MPN
5SL3332-6