It breaks fault currents up to 4.5 kA per EN 60898 and 5 kA per IEC 60947-2, which covers most residential and light commercial panelboard duty.
Panel fit and derating
Occupies 4 modular-width units (72 mm wide) on a DIN rail. Mount in any position. At 40 °C ambient the 63 A rating derates to 59.85 A; at 45 °C it's 57.96 A — factor that into your load schedule if the panel runs warm. IP20 with conductors connected; overvoltage category III, pollution degree 2 — standard for distribution boards.