Skip to main content
Siemens 5SL3502-7 — 1-Pole MCB (DIN Rail)

Siemens 5SL3502-7 SENTRON MCB, 2A C-Curve 1P+N, 230V

MPN5SL3502-7

Siemens SENTRON 5SL3502-7 miniature circuit breaker, 1P+N, 2 A, C-curve, 230 V AC, 4.5 kA per EN 60898, 2 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3502-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityResidential buildings/infrastructure
5SL3502-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL3502-7 — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL3502-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL3502-7 is a SENTRON miniature circuit breaker rated 2 A with a C-curve trip characteristic, in a 1P+N (2-pole) configuration that switches both phase and neutral on a 230 V AC single-phase supply. It breaks faults at 4.5 kA per EN 60898 and 5 kA per IEC 60947-2, covering residential and light commercial infrastructure panels.

The 2 A rating is the continuous current at 30 °C — derate to 1.9 A at 40 °C and 1.75 A at 55 °C (–), so a warm panel or high-ambient enclosure needs headroom. The 1P+N design switches the neutral pole along with the phase — required in many residential codes for single-phase final circuits so the neutral is not left floating when the breaker opens. The 2-module-width footprint on DIN rail matches standard panel layout; 36 mm wide and 76 mm deep with 70 mm installation depth. Breaking capacity of 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 is typical for residential distribution boards where the prospective short-circuit current stays below those levels. If your utility transformer is close or the service entrance has higher fault current, step up to a 6 kA or 10 kA rated breaker.

Deployment context

Snap-on DIN-rail mount (: any position), IP20 with connected conductors — intended for enclosed distribution boards, not open-panel washdown areas.

Frequently asked questions

What is the closest functional second-source to 5SL3502-7?

The 5SL6516-6YA is a sibling in the same SENTRON 5SL family with identical 1P+N footprint and 230 V AC rating, but it is a 16 A B-curve breaker. It will not drop in as a direct replacement for a 2 A C-curve circuit — the current rating and trip curve are different. For a 2 A C-curve substitute, look at other 5SL C2A 1P+N variants within the same series.

Where can I buy 5SL3502-7 and how is it quoted?

We source and quote the 5SL3502-7 to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and we will respond with a firm offer.

What compliance documentation does Siemens provide for 5SL3502-7?

The 5SL3502-7 carries the SENTRON brand and is designed to EN 60898 and IEC 60947-2. It is halogen-free and silicon-free, which supports RoHS and REACH compliance declarations. Standard Siemens documentation includes a CE declaration of conformity and the product datasheet.

MPN
5SL3502-7