Skip to main content
Siemens 5SL3520-6 — 1-Pole MCB (DIN Rail)

Siemens 5SL3520-6 SENTRON MCB, 20 A, B Curve, 2-Pole, 4.5 kA

MPN5SL3520-6

Siemens SENTRON 5SL3520-6, miniature circuit breaker, 2-pole (1P+N), 20 A, B characteristic, 4.5 kA per EN 60898, 230 V AC, 36 mm wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3520-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityResidential buildings/infrastructure
5SL3520-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)4.5 kA
Overvoltage category3
5SL3520-6 — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SL3520-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL3520-6 is a 2-pole (1P+N) miniature circuit breaker from the SENTRON 5SL series, rated 20 A with a B tripping characteristic and a 4.5 kA breaking capacity per EN 60898 and IEC 60947-2. It operates at 230 V AC single-phase, with a maximum DC rating of 60 V.

The 5SL3520-6 occupies 2 width units (36 mm) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm. Terminal capacity accepts solid or stranded conductors from 0.75 to 25 mm², with a tightening torque of 2.5 to 3 N·m. IP20 protection applies with conductors connected — standard for enclosed distribution boards. The neutral conductor is switched (1P+N), so it disconnects both line and neutral on overcurrent or fault.

Frequently asked questions

Where can I buy the 5SL3520-6?

The 5SL3520-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the 5SL3520-6?

The 5SL3520-6 has a 4.5 kA breaking capacity per both EN 60898 and IEC 60947-2.

What wire sizes does the 5SL3520-6 accept?

The terminals accept solid or stranded conductors from 0.75 to 25 mm².

MPN
5SL3520-6