What this 25 A B-curve MCB is for
The 25 A continuous rating is the load it can carry without nuisance tripping in a 30 °C ambient — derate if you're packing it into a hot enclosure. The B curve (3-5x In magnetic trip) is deliberate: it avoids nuisance trips on inrush from small motors or capacitive loads while still protecting wiring. The 1P+N form factor means it occupies 2 width units (36 mm) on a DIN rail, and with an installation depth of 70 mm (76 mm overall) it fits standard distribution boards without a deep enclosure. Wire range accepts 0.75 to 25 mm² solid or stranded, with a tightening torque of 2.5 to 3 N·m on the screw terminals — common for panel wiring up to 6 mm² tails.