It switches the neutral conductor (1P+N configuration) and is rated for 230 V AC single-phase operation, with a maximum breaking capacity of 4.5 kA per both EN 60898 and IEC 60947-2.
Wire terminals accept solid or stranded copper from 0.75 mm² up to 25 mm², with a recommended tightening torque of 2.5 to 3 N·m. The screw terminals are sealable, which matters for installations requiring tamper-proof covers after commissioning.
Rated for ambient temperatures from -25 °C to +45 °C, with periodic excursions to +55 °C and up to 95% humidity. Storage range is wider at -40 °C to +75 °C.