Siemens 5SL3550-7 SENTRON MCB – 50 A, C-Curve, 1P+N
The 4.5 kA breaking capacity per EN 60898 covers most domestic fault levels; the 5 kA per IEC 60947-2 gives a second reference for industrial coordination studies.
Temperature derating — the number that decides the real ampacity
At 40 °C the breaker is good for 46.97 A; at 45 °C it drops to 45 A; at 55 °C it is 42.01 A. Size the upstream conductor and load accordingly.
Mounting position is any, and with connected conductors the IP20 protection applies. The neutral pole is switched internally, so no separate neutral bar connection is needed for the load side — just the incoming neutral lands on the breaker's neutral terminal.