Skip to main content
Siemens 5SL3602-7 — 4-Pole MCB (DIN Rail)

Siemens 5SL3602-7 SENTRON MCB, 4P C-curve 2 A, 4.5 kA

MPN5SL3602-7

Siemens SENTRON 5SL3 series, 5SL3602-7 miniature circuit breaker, 4-pole 3P+N, tripping characteristic C, rated current 2 A AC, breaking capacity 4.5 kA per EN 60898 and IEC 60947-2, 400 V AC rated voltage, 76 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3602-7 — Identification
ParameterValue
Type / order code5SL3
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL3602-7 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC2 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)60 V
Voltage typeAC
Rated frequency50 Hz
5SL3602-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 608984.5 kA
Rated breaking capacity, per IEC 60947-24.5 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SL3602-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
SealableYes
5SL3602-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity
5SL3602-7 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The Siemens 5SL3602-7 is a SENTRON 5SL3-series miniature circuit breaker — 4-pole, 3P+N, with a C-curve trip characteristic and a 2 A rated current at 400 V AC.

Wire terminals accept 0.75 to 25 mm² solid or stranded copper, tightened to 2.5–3 N·m. The neutral pole switches (3P+N), so you get a switched neutral on the same frame — no separate N bar needed downstream.

Siemens rates this breaker for residential buildings and infrastructure — think apartment risers, small commercial subpanels, or lighting and receptacle circuits in a light industrial setting. The 2 A rating is low for a main breaker; it's sized for a subfeed or a dedicated branch like a control transformer primary, a small pump motor, or a bank of LED drivers.

Frequently asked questions

What is the depth of the 5SL3602-7?

The 5SL3602-7 has a depth of 76 mm and an installation depth of 70 mm, fitting standard 100 mm deep enclosures.

What wire sizes does the 5SL3602-7 accept?

The terminals accept solid or stranded copper from 0.75 mm² up to 25 mm², tightened to 2.5–3 N·m.

Where can I buy the 5SL3602-7 and get current pricing?

The 5SL3602-7 is sourced and quoted to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — submit an RFQ for a firm quote.

Will the 5SL3602-7 drop into a panel specified for the 5SL6563-7BB?

Both are 4-pole SENTRON MCBs on the same DIN-rail footprint, but the 5SL6563-7BB carries a different current rating and breaking capacity. Check the specific ratings against your BOM — the physical fit is the same, but the electrical ratings may differ.

MPN
5SL3602-7