Siemens 5SL3616-6 — 4-Pole MCB (DIN Rail)

Siemens 5SL3616-6 SENTRON MCB, 16A 4.5kA B-Curve 4P

MPN5SL3616-6

Siemens SENTRON 5SL3616-6, miniature circuit breaker, 4-pole (3P+N), 16 A, B characteristic, 4.5 kA breaking capacity, 400 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3616-6 — Identification
ParameterValue
Type / order code5SL3
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL3616-6 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC16 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)60 V
Voltage typeAC
Rated frequency50 Hz
5SL3616-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Rated breaking capacity (Icn), per EN 608984.5 kA
Rated breaking capacity, per IEC 60947-24.5 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SL3616-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
SealableYes
5SL3616-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity
5SL3616-6 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Siemens 5SL3616-6 SENTRON MCB — 16 A, B-Curve, 4-Pole, 4.5 kA

The Siemens 5SL3616-6 is a SENTRON 5SL-series miniature circuit breaker rated at 16 A with a B tripping characteristic, designed for 400 V AC nominal supply voltage in 3P+N (4-pole) configuration.

The 4.5 kA breaking capacity (per EN 60898 and IEC 60947-2) tells you the MCB can safely interrupt a fault current up to that level at 400 V AC. If the prospective short-circuit current at the installation point exceeds 4.5 kA, this breaker won't clear the fault within its rated limits — you'd need a higher interrupting rating (e.g., 6 kA or 10 kA) from the 5SL family. The B characteristic means the magnetic trip activates between 3 and 5 times the rated current (48–80 A for this 16 A unit), which is fine for resistive and general loads but too sensitive for motor starting surges. That matters in TN or TT systems where you want the neutral opened and closed with the phases. Terminals accept solid or stranded conductors from 0.75 to 25 mm², with a tightening torque range of 2.5 to 3 N·m. That covers most distribution cable sizes up to 4 mm² for final circuits and 10–16 mm² for sub-mains.

Installation depth is 70 mm (the depth dimension of 76 mm includes the actuator and terminals), which fits standard 100 mm deep distribution boards with room for wiring.

Frequently asked questions

What is the breaking capacity of the 5SL3616-6?

The 5SL3616-6 has a 4.5 kA breaking capacity certified to both EN 60898 and IEC 60947-2 at 400 V AC. This is the maximum fault current it can safely interrupt.

What conductor sizes does the 5SL3616-6 accept?

The terminals accept solid or stranded conductors from 0.75 mm² up to 25 mm². Tightening torque is 2.5 to 3 N·m.

How do I get current pricing and availability for the 5SL3616-6?

Submit an RFQ with your target quantity and delivery timeline. Availability and current pricing are confirmed at quote time through our independent distribution network — no stock count or price figure is published here because both move with the market.

Will the 5SL3616-6 drop into a panel specified around the 5SL3120-6MB?

Both are 4-pole 5SL-series MCBs on the same DIN-rail footprint (72 mm wide, 4 width units), so the mechanical fit is identical. The 5SL3616-6 is a 16 A B-curve; the 5SL3120-6MB is a 20 A B-curve. If the panel was designed for a 20 A circuit, swapping to a 16 A breaker reduces the circuit capacity — verify the load requirement before substituting.