Skip to main content
Siemens 5SL3625-6 — 4-Pole MCB (DIN Rail)

Siemens 5SL3625-6 SENTRON MCB, 4-pole B-curve 25 A, 4.5 kA

MPN5SL3625-6

Siemens SENTRON 5SL miniature circuit breaker, 4-pole (3P+N), B characteristic, 25 A rated current, 4.5 kA breaking capacity per EN 60898, 400 V AC rated voltage.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL3625-6 — Identification
ParameterValue
Type / order code5SL3
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL3625-6 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC25 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)60 V
Voltage typeAC
Rated frequency50 Hz
5SL3625-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Rated breaking capacity (Icn), per EN 608984.5 kA
Rated breaking capacity, per IEC 60947-24.5 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SL3625-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
SealableYes
5SL3625-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity
5SL3625-6 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The Siemens 5SL3625-6 is a 4-pole (3P+N) SENTRON miniature circuit breaker with a B tripping characteristic, rated at 25 A and 400 V AC. Its 4.5 kA breaking capacity per EN 60898 covers most residential and light commercial distribution boards — the B-curve means it trips between 3 and 5 times rated current, suited for resistive and general-purpose loads where inrush is modest.

The 25 A B-curve is a common choice for lighting, socket-outlet, and small-appliance circuits in IEC markets. The 400 V AC rated voltage matches three-phase line-to-line in 230/400 V systems. The 4-pole (3P+N) configuration switches all three phases and the neutral, with the neutral pole switching but not protected — this is standard for TN or TT systems where neutral isolation is required. The neutral conductor switching feature is built in. Terminals accept solid or stranded conductors from 0.75 to 25 mm², tightening torque 2.5 to 3 N·m.

Deployment context

IP20 with connected conductors. Mounting position any.

Frequently asked questions

What conductor sizes does the 5SL3625-6 accept?

Solid and stranded conductors from 0.75 to 25 mm². Terminal torque specification is 2.5 to 3 N·m.

MPN
5SL3625-6