Siemens 5SL4102-8 — 1-Pole MCB (DIN Rail)

Siemens 5SL4102-8 SENTRON MCB, 1P D-curve 2 A, 10 kA

MPN5SL4102-8
Active

Siemens SENTRON 5SL4102-8, 1-pole miniature circuit breaker, D tripping characteristic, 2 A rated current, 10 kA breaking capacity per EN 60898 / IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4102-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityResidential buildings/infrastructure
5SL4102-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SL4102-8 — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL4102-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

1-pole D-curve MCB, 2 A, 10 kA

The Siemens 5SL4102-8 is a SENTRON miniature circuit breaker — 1 pole, D characteristic, rated 2 A at 230/400 V AC. Rated voltage is 250 V single-phase, 440 V multi-phase. The 2 A rating at 30 °C derates to 1.92 A at 40 °C and 1.79 A at 55 °C — relevant if the breaker sits in a crowded enclosure where ambient climbs. DC rating tops at 72 V. Mounting position is unrestricted; the unit occupies 1 modular width (18 mm) on DIN rail.

D-curve selectivity and coordination

The D characteristic is the key selection parameter here. For a 2 A MCB, the magnetic trip threshold sits at 20–40 A instantaneous. That means it ignores the cold inrush of a small control transformer or a 0.75 kW motor start — the kind of load that would trip a C-curve breaker of the same amp rating. Energy limitation class 3 means it lets through less let-through energy (I²t) than class 1 or 2 breakers, which helps downstream semiconductor protection.

IP20 with connected conductors; not rated for washdown.

Frequently asked questions

Where can I buy the 5SL4102-8 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the difference between the 5SL4102-8 and the 5SL6006-7?

The 5SL6006-7 is a 6 A B-curve MCB; the 5SL4102-8 is a 2 A D-curve. They share the same SENTRON platform and 1-module footprint, so the 5SL4102-8 drops into a panel wired for the 5SL6006-7 without rewiring — but the amp rating and trip curve are different, so the circuit protection changes. Verify the load current and inrush profile before swapping.

What compliance documentation does Siemens provide for the 5SL4102-8?

The MCB carries IEC 60898 and IEC 60947-2 ratings, overvoltage category III, pollution degree 2. As a SENTRON component it is CE-marked and RoHS-compliant by default. Specific UL/CSA documentation should be confirmed at order — the evidence does not list UL file numbers.