Siemens 5SL4104-7CC — 1-Pole MCB (DIN Rail)

Siemens 5SL4104-7CC SENTRON MCB, 1P C-curve 4A 10kA

MPN5SL4104-7CC
Active

Siemens SENTRON 5SL4104-7CC, miniature circuit breaker, 1-pole, C characteristic, 4 A rated current, 10 kA breaking capacity per EN 60898, 400 V AC, 1 MW unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4104-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL4104-7CC — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL4104-7CC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL4104-7CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Siemens SENTRON 5SL4104-7CC — 1-pole C-curve MCB, 4 A, 10 kA

The Siemens SENTRON 5SL4104-7CC is a 1-pole miniature circuit breaker with a C tripping characteristic, rated at 4 A and 400 V AC. Its 10 kA breaking capacity per EN 60898 means it safely interrupts short-circuit faults up to that level in residential and infrastructure final circuits — think lighting, socket outlets, or small appliance feeds where the prospective fault current stays under 10 kA.

What the ratings mean for fit

The C-curve (5–10× In) is the standard choice for moderate inrush loads — small motors, transformers, capacitive LED drivers — where a B-curve would nuisance-trip on startup but a D-curve isn't needed. At 4 A it covers a 900 W resistive load at 230 V or a small pump/ventilation fan. The 1-pole form factor (18 mm width, one modular unit) snaps onto a standard DIN rail; the 76 mm depth and 70 mm installation depth leave clearance for a standard distribution board enclosure. Rated for overvoltage category III and pollution degree 2, this MCB is at home in fixed-installation distribution boards where the upstream transformer and service entrance are within the same building. The IP20 rating (with connected conductors) is typical for enclosed panel use — no washdown or outdoor exposure.

Panel integration notes

Mounts in any position on a standard DIN rail. The 18 mm width occupies exactly one modular unit — useful when packing a dense distribution board. Sealable design (tamper-evident cover available) for installations that require lockout. Halogen-free and silicon-free construction matters if the panel is in a clean room or a corrosive environment where outgassing could contaminate contacts. Supplementary devices (auxiliary switches, shunt trips, alarm contacts) can be added on the right side — the product extension flag is set to Yes, so the accessory range for SENTRON 5SL series fits without modification.

Frequently asked questions

What is the breaking capacity of 5SL4104-7CC?

10 kA per EN 60898 at 400 V AC. That is the standard residential/commercial breaking capacity for this class — adequate for most final sub-distribution boards where the upstream transformer limits fault current below that threshold.

Will 5SL4104-7CC drop into a panel built for 5SL4363-7?

No — the 5SL4363-7 is a 3-pole unit (54 mm wide, 3 MW) while the 5SL4104-7CC is 1-pole (18 mm wide, 1 MW). The depth (76 mm) and height (90 mm) are identical, and both share the same SENTRON mounting footprint, but the pole count and width are different. You would need to rewire the circuit and adjust the DIN-rail space allocation.

Where can I buy 5SL4104-7CC and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for this order code and the desk will return a firm price and lead time.

MPN
5SL4104-7CC