Siemens 5SL4106-7CC — 1-Pole MCB (DIN Rail)

Siemens 5SL4106-7CC SENTRON MCB, 1P C-curve 6A 10kA

MPN5SL4106-7CC
Active

Siemens SENTRON 5SL4 series, miniature circuit breaker (MCB), 1-pole, C-curve, 6 A rated, 10 kA breaking capacity, 400 V AC, 72 V DC max, 18 mm wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4106-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL4106-7CC — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL4106-7CC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL4106-7CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL4106-7CC is a SENTRON miniature circuit breaker, 1-pole, C-curve, rated 6 A with a 10 kA breaking capacity per EN 60898. It operates at 400 V AC (single-phase 250 V AC, multi-phase 440 V AC max) and up to 72 V DC. The 18 mm width (1 modular unit) snaps onto a DIN rail — standard panel fit for residential and infrastructure distribution boards.

At 30 °C the breaker carries the full 6 A; at 40 °C it derates to 5.68 A, at 50 °C to 5.35 A.

Snap-on mounting to DIN rail EN 60715, any position. Depth 76 mm, height 90 mm, width 18 mm — one modular unit. Installation depth 70 mm behind the panel surface. IP20 with connected conductors; sealable for tamper-proofing in metering or common-area boards. Halogen-free and silicon-free construction for environments sensitive to outgassing (clean rooms, food processing).

Frequently asked questions

What is the breaking capacity of 5SL4106-7CC?

10 kA per EN 60898 at 400 V AC.

What is the width of 5SL4106-7CC?

18 mm, which is 1 modular unit on a DIN rail.

Does 5SL4106-7CC require derating at elevated ambient temperatures?

Yes — at 40 °C the rated current drops to 5.68 A, at 50 °C to 5.35 A. Size the branch circuit for the derated value if the panel runs warm.

Where can I buy 5SL4106-7CC?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.