Siemens 5SL4110-8 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SL4110-8 MCB, 1P D 10 A, 10 kA, 400 V AC

MPN5SL4110-8
Active

Siemens SENTRON 5SL4110-8, miniature circuit breaker, 1-pole, D tripping characteristic, 10 A rated current, 10 kA breaking capacity at 400 V AC, 50/60 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4110-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL4110-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Energy limitation class3
Overvoltage categoryIII
5SL4110-8 — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL4110-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SL4110-8 is a 1-pole miniature circuit breaker (MCB) with a D tripping characteristic, rated at 10 A and 400 V AC, with a 10 kA breaking capacity per EN 60898 and IEC 60947-2. That D-curve means it's built for loads with high inrush — motor starters, transformers, discharge lighting — where the magnetic trip holds off until roughly 10 to 20 times rated current, so nuisance tripping on startup doesn't happen.

Sealable, halogen-free, silicon-free — that's a plus for clean-room or low-corrosion environments where outgassing matters.

Ratings that matter for selection

The 10 A rating is at 30 °C; at 40 °C it derates to 9.24 A, at 45 °C to 8.8 A, at 55 °C to 7.96 A. If your panel ambient runs warm, size the breaker one step up or account for the derate. DC rating is 72 V maximum — useful for control circuits but not for 125 V DC battery banks.

Frequently asked questions

How do I get current pricing and availability for 5SL4110-8?

Pricing and availability are confirmed at quote time. Submit an RFQ against this order code and we'll source it through independent distribution channels.

What is the difference between 5SL4110-8 and 5SL6120-7?

The 5SL6120-7 is a 2-pole, 20 A, C-curve MCB — different poles, current, and trip characteristic. The 5SL4110-8 is 1-pole, 10 A, D-curve. They are not drop-in replacements; the panel wiring and coordination study would need to match the specific rating.

What compliance documentation does Siemens provide for 5SL4110-8?

The 5SL4110-8 carries ratings per EN 60898 and IEC 60947-2, with a 10 kA breaking capacity. It is halogen-free and silicon-free. Standard Siemens documentation includes a declaration of conformity and test certificates; request these with your RFQ.

MPN
5SL4110-8