Siemens 5SL4116-7CC — 1-Pole MCB (DIN Rail)

Siemens 5SL4116-7CC SENTRON MCB, 1P C16, 10kA

MPN5SL4116-7CC
Active

Siemens SENTRON 5SL4116-7CC, miniature circuit breaker, 1-pole, C-curve, 16 A rated, 10 kA breaking capacity per EN 60898, 1 MW width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4116-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL4116-7CC — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL4116-7CC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL4116-7CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SL4116-7CC is a 1-pole miniature circuit breaker rated 16 A with a C tripping characteristic, designed for residential and infrastructure branch-circuit protection. Its 10 kA breaking capacity per EN 60898 at 400 V AC clears fault currents up to that level without upstream coordination issues in most domestic and light commercial panels. Rated voltage is 250 V AC single-phase, 440 V AC multi-phase. Thermal derating is published: at 40 °C ambient the continuous rating drops to 14.78 A, at 50 °C to 13.45 A. Panel builders should factor this when packing enclosures. Installation depth is 70 mm, overall depth 76 mm — fits flush in most 80 mm deep enclosures. IP20 with conductors connected; touch protection is integrated.

Frequently asked questions

What is the breaking capacity of 5SL4116-7CC?

The 5SL4116-7CC is rated 10 kA breaking capacity per EN 60898 at 400 V AC, sufficient for most residential and light commercial fault-level requirements.

What is the width of 5SL4116-7CC?

The 5SL4116-7CC is 18 mm wide, occupying 1 modular width unit on a standard DIN rail.

Where can I buy 5SL4116-7CC?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

Will 5SL4116-7CC drop into a panel specified for 5SL4120-7CC?

Yes, the 5SL4116-7CC shares the same 18 mm width, DIN-rail mounting, and SENTRON platform as the 5SL4120-7CC. The only difference is the current rating — 16 A vs 20 A — so no rewiring is needed for the same form factor.

MPN
5SL4116-7CC